Module Mitsubishi QX41Y41P
Input: 32 points, 24 V DC, 4 mA, response time: 1/5/10/20/70 ms, 32 points/common, positive common;
output: 32 points, 12 to 24 V DC, 0.1 A/point, 2 A/common, response time: 1 ms, 32 points/common, sink type;
40-pin connector, with thermal and short-circuit protection and surge suppressor
Module Mitsubishi QX48Y57
Input: 8 points, 24 V DC, 4 mA, response time: 1/5/10/20/70 ms, 8 points/common, positive common;
output: 7 points, 12 to 24 V DC, 0.5 A/point, 2 A/common, response time: 1 ms, 7 points/common, sink type;
18 points terminal block, with surge suppressor and fuse
Module Output Mitsubishi QH42P
Input: 32 points, 24 V DC, 4 mA, response time: 1/5/10/20/70 ms, 32 points/common, positive common;
output: 32 points, 12 to 24 V DC, 0.1 A/point, 2 A/common, response time: 1 ms, 32 points/common, sink type;
40-pin connector, with thermal and short-circuit protection and surge suppressor
Module Output Mitsubishi QY81P
32 points, 12 to 24 V DC, 0.1 A/point, 2 A/common, response time: 1 ms, 32 points/common, source type, 32-pin D-sub connector,
with thermal and short-circuit protection and surge suppressor
Module Output Mitsubishi QY71
32 points, 5 to 12 V DC, 16 mA/point, 512 mA/common, response time: 0.5 ms, 32 points/common, sink type, 40-pin connector,
with fuse
Module Output Mitsubishi QY70
16 points, 5 to 12 V DC, 16 mA/point, 256 mA/common, response time: 0.5 ms, 16 points/common, sink type,
18-point terminal block, with fuse
Module Output Mitsubishi QY68A
8 points, 5 to 24 V DC, 2 A/point, 8 A/module, response time: 10 ms, sink/source type, 18-point terminal block,
with surge suppressor, all points independent
Module Input Mitsubishi QY50
16 points, 12 to 24 V DC, 0.5 A/point, 4 A/common, response time: 1 ms, 16 points/common, sink type,18-point terminal block,
with surge suppressor and fuse
Module Input Mitsubishi QY42P
64 points, 12 to 24 V DC, 0.1 A/point, 2 A/common, response time: 1 ms, 32 points/common, sink type, 40-pin connector,
with thermal and short-circuit protection and surge suppressor
Module Input Mitsubishi QY41P
32 points, 12 to 24 V DC, 0.1 A/point, 2 A/common, response time: 1 ms, 32 points/common, sink type, 40-pin connector,
with thermal and short-circuit protection and surge suppressor
Module Input Mitsubishi QY40P
16 points, 12 to 24 V DC, 0.1 A/point, 1.6 A/common, response time: 1 ms, 16 points/common, sink type, 18-point terminal block,
with thermal and short-circuit protection and surge suppressor
Module Input Mitsubishi QY22
16 points; 100 to 240 V AC; 0.6 A/point; 4.8 A/common; minimum load voltage/current: 24 V AC/100 mA, 100 to 240 V AC/25 mA;
response time: 1 ms + 0.5 cycle, 16 points/common, 18-point terminal block, with surge suppressor